MIL-STD-188-154A
Transmission
Access
Transmission
Access
xC
Dist xC Frame
Horiz
Multiplexer
Trunk
Dist
Frame xC
Horiz
xC
Access may be integrated into equipment
Access may be integrated into equipment
Circuit Access Point
xC Cross-Connect
FIGURE 5. Multiplexer connections.
5.3.1.4.2 Smart multiplexer. A circuit connected to a smart multiplexer shall be wired from the distribution frame to the circuit access point associated with the proper port of the multiplexer. High priority circuits may be provided with automatic switchover to an alternate port, in lieu of a physical patch. Provisions shall be made for testing both the circuit traffic and the physical path. The inputs to the multiplexer may be original digital circuit, output of the conditioning string, multiplexed output from another multiplexer, output of a matrix switch, or interswitch trunk output of a digital switch. The output of the multiplexer shall be wired to a distribution frame. Figure 6 shows the normal circuit flow and access required for connection to a smart multiplexer.
17