MIL-STD-188-154A
User Access
Commercial
Circuit
xC Commercial xC
POP
Base
Cable
In-station
Equipment
Distribution
Frame
- Vertical
Distribution
Frame xC -Horizontal
xC
Distribution
Frame
-Horizontal xC
xC
Circuit Access Point
Access may be integrated into equipment such as a DACCS
xC Cross-Connect
FIGURE 2. Digital circuit - user access portion.
5.3.1.2 Interface equipment. The circuit shall be wired from the distribution frame to the required interface equipment string. This string shall include line access equipment (channel service units/data service units (CSU/DSUs), modems, line drivers, etc.), conditioning equipment (regenerative repeaters, protocol converters, etc.), and cryptographic equipment as required. Capabilities for circuit testing and patching shall be provided between each piece of equipment to allow for fault isolation and equipment substitution. This may be achieved by wiring back to a distribution frame for connection to manual
patch panels or electronic access points or by using access points integral to the installed equipment. After transiting the interface string, the circuit will be in a format suitable for connection to a multiplexer, digital switch, cable access equipment, or commercial access equipment. The circuit shall then be wired to the distribution frame for connection to the next applicable equipment item. Figure 3 shows the normal circuit flow for the interface equipment portion of a digital circuit. All circuits leads shall be cross connected and shall appear at the circuit access point.
14
For Parts Inquires call Parts Hangar, Inc (727) 493-0744
© Copyright 2015 Integrated Publishing, Inc.
A Service Disabled Veteran Owned Small Business